BATCHEN WATER BATH VAPORISERS are designed to meet relevant Australian pressure vessel and electrical standards and conform to the requirements of AS1596 L P Gas - Storage and Handling. Flameproof electrical design allows vaporisers to be installed close to storage tanks. |
|
|
|
|
|
|
SAFETY FEATURES
The water bath vaporiser uses water as a heat transfer medium, thus, creating a safe mode of heat transfer to vaporise LPG. Safety Features include:
Excess flow Valves
LPG Safety Relief Valves
Water Safety Relief Valve
In an event of a leakage from the LPG coils, a vapour detection vessel (VDV) consisting of a float switch to raises an audible alarm and shuts off vaporiser, remote hot water pumps and hot water heaters. The float switch shall be interfaced with site emergency shutdown system.
|
|

|
|
|
|
|
|
|
|

CLICK TO VIEW FULL DRAWING
|
|
| Hot water system is designed for –10C LPG inlet and +30C outlet |
| Capacity Litre/hr |
Hot Water Requirement |
LPG coil sP |
Dimensions |
Mass (kg) |
| Propane |
Propane/Butane
|
Butane |
GJ/hr1 |
Flow L/m |
kPa |
A |
B |
Inst'd |
Tare |
ship'd |
| 550 |
500 |
500 |
0.138 |
53 |
3 |
3100 |
1600 |
1450 |
950 |
1350 |
| 1100 |
1100 |
1000 |
0.276 |
106 |
7 |
3950 |
2000 |
1700 |
1050 |
1500 |
| 1650 |
1650 |
1500 |
0.414 |
159 |
20 |
4600 |
2400 |
1900 |
1200 |
1700 |
| 2200 |
2200 |
2000 |
0.552 |
212 |
36 |
5260 |
2700 |
2100 |
1300 |
1850 |
| 3300 |
3300 |
3000 |
0.828 |
318 |
89 |
6290 |
3200 |
2450 |
1450 |
2100 |
| 4400 |
4000 |
4000 |
1.104 |
424 |
164 |
7470 |
4000 |
2850 |
1650 |
2500 |
|